| Power Rating |
3, 5, 7.5, 10, 12.5, and 15 KW |
| Input Voltage |
3 & 5 KW;120, 208, 240, or 277 VAC (-20% to
+15%) |
|
7.5, 10, 12.5, and 15 KW; 208, 240, or 277 VAC (-15% to +15%)
|
| Output Voltages |
3 - 15 KVA/KW; 208, 240, or 277VAC |
Output Frequency (Inverter Operation) |
60 Hz ±0.5 Hz |
| Voltage Regulation |
±3%, Regulated within CBEMA curve |
| Output Wave Form |
Sine-Wave < 5% THD. |
| Efficiency |
Minimum 90% |
| Crest Factor |
3:1 Typical |
| Surge Protection |
The UPS will protect itself and the load against surges
as defined in ANSI/IEEE C62.41 Categories A and B. |
| Isolation |
Output is completely isolated from input, and with multi
voltages, when input & output is different.
|
| Noise Isolation |
-120 dB Common-Mode;
-60 dB Transverse-Mode |
| Battery |
Sealed maintenance-free (AGM) battery |
| Recharge Current |
Conforms to UL Standards |
| External Battery |
Provisions for hardwire connection of optional external
battery cabinets or DC source. |
| Environmental |
| Humidity |
0 - 95% RH w/ no condensation |
| Operating Temperature |
UPS: 0° to 40°C. (32° - 104°F)
Battery: 20° to 30°C. (68° - 86°F) |
| Storage Temperature |
-20 to 60°C. (-4° - 140°F) |
| Altitude |
Up to 10,000 ft |
| Safety Agencies |
CUL, CSA Listed UL1778, UL924, UL924A,, MEA Approved;
State Fire Marshal Approved (CA, NY, IL) |
| *Inverter Cabinet Sizes (with Standard Battery
Run Times) All model |
|
|
W" |
|
H" |
|
D" |
| 3 kW |
39 |
x |
48 |
x |
18 |
| 5 - 15 kW |
39 |
|
68 |
|
18 |
|
| *Battery Cabinet Sizes (with
Standard Battery Run Times) |
|
|